UL Labeled Underground Fiberglass Fuel Tanks

Alltankscom - Tanksystems Div... Call Free Today  800 537 9444    Rainwater University

    Pictures of Tanks, Mixers, Pumps, Systems & Tank Fittings                     Home

Water Tanks  poly tanks are UV resistant, NSF, FDA certified for use in food and drinking water storage

Plastic Tanks  the storage container for  most chemicals.

site map

Water Tanks

Water  Designs

Rain Water  

Exxon NSF 61 Cert

NSF Resin

Water Softener

Fire Water

Keep Algae Out

Rainwater Manual

H20 Tank

Terminology

Underground

 

Chemical Tanks

Underground Tanks

Double Wall

Fiberglass 

Underground FRP

Ladders & Tie Down

Chemical Tanks

Caustic & Bleach

Waste Water

Treatment

Design & Specs

 Chemical Resistance Chart

ASTM-1998-97 Specs

Plastic tank Drawings

Installation Instructions

Process Connections  

Poly Tank Mfg

FDA/CFR/Best Practice

Customer...FAQ

Polyethylene...Definition

Tank... Inspections 

Biodiesel...

Herbicide...Spray       

Free. Tank. Drawing     

Pumps & Skids

Polyethylene. Plastic  

MSDS

Other Products

RavenTank.com

Centrifugal Casting

Tank Inspection

 

Pictures

Bilge Water Systems

Agitators - Mixer

Pictures

Pictures A

Deicing System

Mag Chlor Storage

Fire Water

Margarita World Record

Porter SUD Tank

The Holy Cow

News.com

Biodiesel System

Pics

 

 

  Current Mailer 

 

 


UL Labeled & to NFPA                        

Guide Specifications – Double-Wall FRP Tanks for Fuel Storage

 

Short Form

The contractor shall provide a double-wall fiberglass reinforced plastic (FRP) Underwriters Laboratories-labeled underground storage tank as shown on the drawings.

The tank size, fittings and accessories shall be as shown on the drawings. The fiberglass tank shall be provided  by AlltanksCom of Houston Texas 800 537 9444

The tank shall be tested and installed according to the Xerxes Installation Manual and Operating Guidelines for Single-Wall and Double-Wall Fiberglass Underground Storage Tanks in effect at time of installation.

Part I: General

1.01 Quality Assurance

A.  Acceptable Manufacturer: Xerxes Corporation

B.  Governing Standards, as applicable:

1.   Underwriters Laboratories (UL) Standard for Safety 1316, File MH 9061 for storage of flammable liquids. A UL label shall be attached to each tank.

2.   National Fire Protection Association (NFPA) Standards:

                                NFPA 30: Flammable and Combustible Liquids Code   

                                NFPA 30A: Automotive and Marine Service Station Code         

                                NFPA 31: Installation of Oil-Burning Equipment.

3.   City of New York Department of Buildings M.E.A., Division #161-89-M.

4.   Los Angeles Fire Department.

Part II: Products

2.01 Double-Wall Fiberglass Reinforced Plastic (FRP) Underground Storage Tanks

A.  Loading Conditions – Tank shall meet the following design criteria:

1.   Internal Load – Tank certified to pass a maximum 5-psig air-pressure test with 5:1 safety factor. Contractor shall individually test tanks for leakage prior to installation.

2.   Vacuum Test – To verify structural integrity, every standard 10'-diameter tank and smaller shall be vacuum tested by the manufacturer at the factory to 11.5" of mercury.

3.   Surface Loads – Tank shall withstand surface H-20 axle loads when properly installed according to manufacturer's current Installation Manual and Operating Guidelines.

4.   External Hydrostatic Pressure – Tank shall be capable of being buried in ground with 7' of  overburden over the top of the tank, the hole fully flooded and a safety factor

of 5:1 against general buckling.

5.   Tank shall support accessory equipment – such as heating coils, drop tubes, submersible pumps and ladders – when installed according to tank manufacturer’s current Installation Manual

and Operating Guidelines.

B.  Product Storage

1.   Tank shall be capable of storing petroleum products with specific gravity up to 1.1.

2.   Tank shall be vented to atmospheric pressure.

3.   Tank shall be capable of storing products identified in the manufacturer’s current standard limited warranty.

C.  Materials

1.   Tank shall be manufactured with 100% resin and glass-fiber reinforcement. No sand fillers.

D.  Tank Dimensions (Refer to Xerxes literature on gallonage.)

1.   Tank shall have nominal capacity of _____ gallons.

2.   Tank shall have nominal outside diameter of _____ feet.

E.  Interstitial Space

1.   Tank shall have a space between the primary and secondary walls to allow for the free flow and containment of leaked product from the primary tank. The space also allows the

insertion of a monitoring device through a monitoring fitting.

2 Accessories

A.  Optional Anchor Straps

1.   Straps shall be FRP anchor straps as supplied by tank manufacturer.

2.   Number and location of straps shall be specified in current literature by tank manufacturer.

B.  Manways

1.   All manways shall be flanged and 22" I.D., complete with UL-listed gaskets, bolts and covers. (30" and 36" I.D. manways are also available on certain larger tanks.)

2.   Location is shown on tank drawings.

3.   Optional manway extensions shall be FRP and 24" long.

C.  Optional Fill Tubes

1.   Fill tubes shall be FRP, 4"-diameter, with a 6" x 4" double-tapped reducer bushing, and include a 6" NPT fitting. Tubes shall terminate a minimum of 4" from the bottom of tank (a

minimum of 6" for a 12'-diameter tank).

D.  Gauge Plates

1.   Gauge plates shall be installed under each service fitting and manway opening.

E.  Optional Heating Coils

1.   Optional heating coils shall be installed in a separate 22" manway and shall be as supplied by tank manufacturer.

F.  Optional Ladders

1.   Ladders shall be the standard ladder as supplied by tank manufacturer (aluminum, carbon steel or fiberglass).

G.  NPT Threaded Fittings

1.   All standard threaded fittings shall be half-couplings and shall be 4"- or 6"- diameter. Reducers are to be used for smaller sizes where shown and provided by contractor.           

2.   Strength – NPT fittings shall withstand a minimum of 150 foot-pounds of torque and 1,000 foot-pounds of bending, both with a 2:1 safety factor.

H.  Monitor Fittings

1.   Each monitor fitting shall consist of a 4" NPT fitting on the tank. Tanks with a hydrostatic monitoring system do not have a monitor fitting.

 

Part III: Testing and Installation

3.01 Testing

A.  Tank shall be tested according to the Xerxes Installation Manual and Operating Guidelines for Single-Wall and Double-Wall Fiberglass Underground Storage Tanks in effect at time of installation.

3.02 Installation

A.  Tank shall be installed according to the Xerxes Installation Manual and Operating Guidelines for Single-Wall and Double-Wall Fiberglass Underground Storage Tanks in effect at time of installation.

B.  Contractor shall be trained by the tank manufacturer, the state or other approved agency.

Part IV: Warranty

4.01 Warranty

A.  Warranty shall be manufacturer's limited warranty for double-wall underground petroleum tanks in effect at time of purchase.

 