Guide Specifications – Single Wall FRP
Short
Form
The
contractor shall provide a fiberglass reinforced plastic (FRP) underground
storage tank as shown on the drawings.
The tank
size, fittings and accessories shall be as shown on the drawings. The fiberglass
tank shall be provided by AlltanksCom of Houston Texas 800 537 9444
The tank
shall be tested and installed according to the AlltanksCom Installation Manual and
Operating Guidelines for Single-Wall and Double-Wall Fiberglass Underground
Storage Tanks in effect at time of installation.
Note: All Potable Water Storage
Tanks must be Steam Cured for a minimum of 36 consecutive hours.
Part I: General
1.01
Quality Assurance
A. Acceptable Manufacturer: AlltanksCom 800 537 9444
B. Governing Standards, as applicable: ASTM
Part II: Products
2.01
Single Wall Fiberglass Reinforced Plastic (FRP) Underground Storage Tanks
A. Loading Conditions – Tank shall meet the
following design criteria:
1. Internal Load – Tank certified to
pass a maximum 5-psig air-pressure test with 5:1 safety factor. Contractor shall
individually test tanks for leakage prior to installation.
2. Vacuum Test – To verify
structural integrity, every standard 10'-diameter tank and smaller shall be
vacuum tested by the manufacturer at the factory to 11.5" of mercury.
3. Surface Loads – Tank shall
withstand surface H-20 axle loads when properly installed according to
manufacturer's current Installation Manual and Operating Guidelines.
4. External Hydrostatic Pressure –
Tank shall be capable of being buried in ground with 7' of overburden over
the top of the tank, the hole fully flooded and a safety factor
of 5:1 against general buckling.
5. Tank shall support accessory
equipment – such as heating coils, drop tubes, submersible pumps and ladders –
when installed according to tank manufacturer’s
current Installation
Manual and Operating Guidelines.
B. Product Storage
1. Tank shall be capable of storing
potable drinking water with a specific gravity up to 1.1.
2. Tank shall be vented to
atmospheric pressure.
3. Tank shall be capable of storing
products identified in the manufacturer’s current standard limited warranty.
C. Materials
1. Tank shall be manufactured with
100% resin and glass-fiber reinforcement. No sand fillers.
2 Accessories
A. Optional Anchor Straps
1. Straps shall be FRP anchor straps
as supplied by tank manufacturer.
2. Number and location of straps
shall be specified in current literature by tank manufacturer.
B. Manways
1. All manways shall be flanged and
22" I.D., complete with UL-listed gaskets, bolts and covers. (30" and 36" I.D.
manways are also available on certain larger tanks.)
2. Location is shown on tank
drawings.
3. Optional manway extensions shall
be FRP and 24" long.
C. Optional Fill Tubes
1. Fill tubes shall be FRP,
4"-diameter, with a 6" x 4" double-tapped reducer bushing, and include a 6" NPT
fitting. Tubes shall terminate a minimum of 4" from the bottom of tank (a
minimum of 6" for a 12'-diameter tank).
D.
NPT Threaded Fittings
1. All standard threaded fittings
shall be half-couplings and shall be 4"- or 6"- diameter. Reducers are to be
used for smaller sizes where shown and provided by contractor.
2. Strength – NPT fittings shall
withstand a minimum of 150 foot-pounds of torque and 1,000 foot-pounds of
bending, both with a 2:1 safety factor.
Part III: Testing and
Installation
3.01
Testing
3.02
Installation
A. Tank shall be installed
according to the AlltanksCom Installation Guidelines for Single-Wall Fiberglass
Underground Storage Tanks in effect at time of installation.
B. Contractor shall be
trained by the tank manufacturer, the state or other approved agency.
Part IV:
Warranty
4.01
Warranty
A. Warranty shall be manufacturer's limited 2 year warranty for single
underground water tanks in effect at time of purchase.